DMTFF
FLANGED TRANSIT-TIME ULTRASONIC FLOWMETER |
Four lines 16 alphabetical LCD display
Suitable for liquids of high temperature of -40~150 deg C
Multiple outputs including Hart and ModBus outputs
High accuracy by calibrated with flanged pipe in lab |
|
DMTF transit time flow meter utilizes two transducers that function as both ultrasonic transmitters and receivers. The transducers are clamped on the outside of a closed pipe at a specific distance from each other. The transducers can be mounted in V-method in which case the ultra sound transverses the pipe twice, or W-method in which case the ultra sound transverses the pipe four times, or in Z-method in which case the transducers are mounted on opposite sides of the pipe and the ultra sound transverses the pipe only once. The selection of mounting method depends on pipe and liquid characteristics. When the flow meter works, the two transducers transmits and receives ultrasonic signal amplified by multibeam that travels firstly downstream and then upstream (Figure 1). Because ultra sound travels faster downstream than upstream, there will be a difference of time of flight(¡÷£ô). When the flow is still, the time difference(¡÷£ô) is zero. Therefore, as long as we know the time of flight both downstream and upstream, we can work out the time difference, and then the flow velocity (V) and flow volume (Q) via the following formula.

V= K*D* dt Where: V: Liquid velocity K: Constant D: Distance between the two transducers dt: difference in time of flight
|
Features:
1. Calibrated in manufacture's lab, field setup is unnecessary.
2. Measurement is independent of fluid nature with wider applications than magnetic meters.
3. Available including up to 8GB event data logger, can search the¡¡event of totalizer flow, flow rate, velocity etc.¡¡
4. Parallel operation of positive, negative and net flow totalizer, while the output of totalizer pulse and frequency output are transmitted via open collector.
5. Re-calibration or maintenance is easy, no processing interruption (just plug out the inserted transducers from pipe line, when re-calibration or maintenance is finished), can be hot-tapped.
|
|
Transmitter |
Power Supply |
(Std) 10-28 VDC @ 2.5VA max.115/230VAC 50/60Hz ¡À15%@ 5VA max. Solar energy |
|
Velocity |
0 ~ ¡À40 ft/s (0 ~ ¡À12m/s), bi-directional |
|
Display |
4 line¡Á16 English letters LCD back lit, can display total flow, flow rate, velocity and meter running status etc. |
|
Units
Rate
Totalized |
User Configured (English and Metric);
Rate and Velocity Display;
(FWD, NET, REV or BATCH) gallons, ft³, barrels, lbs, litters, m³,kg |
|
Output |
4~20mA, Pulse, Relay, RS232C or RS485, options: up to 8 GB Data logger, Hart +(4~20mA), Modbus |
|
Accuracy |
¡À1.0% of reading at rates >0.5 m/s); |
|
¡À0.005 m/s of reading at rates<0.5 m/s |
|
Sensitivity |
Flow Rate: 0.001f/s (0.0003m/s) |
|
Repeatability |
0.2% of reading |
|
Security |
Keypad lockout, access code enable |
|
Dimensions |
Std.:242*190*115 Weight: <2.5kg |
|
Exp: 255*220*110 Weight: <5.0kg |
|
Transducer |
Liquid Types Supported |
Virtually most any liquid containing less than 2% total suspended solids (TSS) or aeration |
|
Suited Liquid Temperature |
Std. Temp. Transducer: -40¡æ~121¡æ
High Temp. Transducer : -40¡æ~150¡æ |
|
Cable Length |
Std: 20 feet (6m); Opt: Maximum: 990 feet (300m) |
|
Pipe Size |
ND65~ND3000; select S type flange transducers if pipe |
|
DMTFF Flanged Ultrasonic Flow Meter Selection Table
Model DMTFF ¨C X ¨C X X X X *£¨Transducers£©
|
Flanged Series |
|
|
Approvals |
|
|
N¡ªN/A |
|
|
Ex¡ªExdIIBT6 |
|
|
Power Supply |
|
|
A¡ª110VAC |
|
|
B¡ª220VAC |
|
|
E¡ª24VDC |
|
|
Output Selection 1 |
|
|
N¡ªN/A |
|
|
1¡ª4-20mA |
|
|
2¡ªPulse Output£¨Flow Rate or Totalizer Output£© |
|
|
3¡ªRelay |
|
|
4¡ªRS232 |
|
|
5¡ªRS485 |
|
|
6¡ªHart+(4-20mA) |
|
|
7¡ªModBus |
|
|
8¡ªData Logger & Software
9¡ªHeat Flow
(Two loops temperature transmitter 4-20mA input) |
|
|
Output Selection 2 |
|
|
Same as Output Selection 1 |
|
|
Output Selection 3 |
|
|
Same as Output Selection 1 |
|
|
|
|
|
|
|
|
|
|
|
Transducer Selection Table of DMTFF Insertion Ultrasonic Flow Meter
|
DC - X - X - X - X - X |
|
|
|
|
|
|
|
|
Flanged Series |
|
|
Transducer Type |
|
|
0¡ªCommon flanged type (65-2000mm) |
|
|
1¡ªS-Series small flanged type (20-65mm) |
|
|
2¡ª Very low flow rate flanged type (15-50mm) |
|
|
Pressure Level |
|
|
A¡ª1.0MPa |
|
|
|
B¡ª1.6 MPa |
|
|
C¡ªPlease contact the factory if High Pressure |
|
|
Pipeline Material |
|
|
|
|
0¡ªCarbon Steel |
|
|
|
|
1¡ªStainless Steel |
|
Pipeline Diameter |
|
0012¡ªDN12 |
|
|
1200¡ªDN1200 |
|
|
Cable Length |
|
|
XXX (meter)
The Maximum can reach to 300m, also can contact with the factory for details. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parts Number Construction example: For example: DMTFF¨CN-B1NN-N/DF-0-B-0-0400-030 Note: DMTF Flanged ultrasonic flow meter, 220VAC power supply, 4-20mA output, non-multiple output selection; common pipeline Flange mounting transducer, pressure is 1.0Pa, pipeline is ND400, transducer cable length is 30m. |
|
|
|