Download DMTFC Catalogue (1,114KB)Transmitter |
Power Supply |
10-28 VDC @3VA max.; 115/230 VAC 50/60Hz 15% @6VA max |
Velocity |
0.03~40ft/s(0.01~12m/s), bi-directional |
|
Display |
LCD with backlight. 220 letters. |
|
Units |
English (U.S.) or metric |
|
Signal Outputs |
Current output:4~20mA |
|
OCT output: pulse signal for accumulated flow rate( positive, negative and net rates); frequency signal for instantaneous flow rate(0~1,000 Hz selectable) |
||
Repeatability |
Better than 0.5% read |
|
Accuracy |
Better than 1.0 % read for velocity above 1.0 ft/s |
|
Response time |
0.5s |
|
Recording |
Automatically record the following information: |
|
Communication |
RS-232, RS-485,Hart&ModBus Protocol Module(optional) |
|
Data Logging |
512M (200,000 event), 16-bit integral DB-9 RS232C Connection can be removed and installed without disconnecting system power |
|
| Enclosure | Protection Class:IP65(NEMA 4X) Explosive Proof Class : EEe XII (for model DMTFC2 only) |
|
Liquids |
Liquid Types |
Virtually most any liquid containing less than 5% total suspended solids (TSS) or aeration. |
Liquid Temp |
(Std) -40 to 180F [-40 to 82], opt -40 to 300F [-40 to 150] |
|
Pipe |
Pipe Size |
(Std) 4 to 120 inches [100 to 3048 mm] pipe I.D. |
Pipe Material |
All metals, most plastics, fiber glass, etc., allow pipe liner. |
|
Straight Pipe |
Section Longer than 8D, where D is pipe diameter. If a pump is near, the straight pipe section following the pump should be >15D. |
|
Cable |
Shielded transducer cable. Standard length 20 (6m). Can be extended to 990 (300 m). Contact the manufacturer for longer cable requirement. |
|
Environment |
Temperature |
Transmitter : -40 to 131F [-40 to 55] |
Transducer : (Std) -40 to 180F [-40 to 82], opt -40 to 300F [-40 to 150] |
||
Humidity |
Transmitter : 0-95% relative humidity, non-condensing |
|
Transducer : 0-95% relative humidity, non-condensing |
||
Weight |
DMTFC1, transmitter 6lb(about 2.7 kg), transducer 4lb(about 1.8 kg, including ball valve) |
|